Skip to content
FREE ACCESS to our RYDM (Rail Yard Data Management) demo website... click to learn more
FREE ACCESS to our RYDM demo website... Rail Yard Data Management

245F Emergency Tank Vent, 8 in, Flanged, Lightweight, Morrison Bros 245F--0800 AV

$225.00
SKU 245F--0800 AV

245F Emergency Tank Vent, 8 in, Flanged, Lightweight, Morrison Bros 245F--0800 AV

Downloads:

Specification Sheet

Quick Specs:

  • Size:  8"
  • Part Number:  245F--0800 AV
  • Manufacturer:  Morrison Bros
  • Series:  Fig. 245F
  • Material:  Aluminum
  • Type:  Emergency Tank Vent

Features & Ordering:

Construction Details

  • Body is aluminum
  • Cover is aluminum
  • Seat is FKM

Code Compliance

When properly sized for the tank, this vent will conform to the requirements of the International Fire Code; National Fire Code of Canada; National Fire Protection Agency—NFPA 20, 30, 30A, 31, 37, 110; Petroleum Equipment Institute—PEI RP200, PEI RP800; Underwriters Laboratories Inc.—UL-142, UL-2085, UL-2244; Underwriters Laboratories of Canada—CAN/ULC S601, CAN/ULC S602, CAN/ULC S652

Approvals

Underwriters Laboratories Inc. UL-2583

Product Ordering Instructions

Fig Suffix Size Screen Weight
Male Threaded models
245M 0200 AV 2” No .50 lbs
245MS 0200 AV 2” Yes .50 lbs
245M 0300 AV 3” No 2.50 lbs
245MS 0300 AV 3” Yes 2.50 lbs
245M 0400 AV 4” No 4.50 lbs
245MS 0400 AV 4” Yes 4.50 lbs
245M 0600 AV 6” No 6.20 lbs
245MS 0600 AV 6” Yes 6.20 lbs
245M 0800 AV 8” No 10.10 lbs
Female Threaded models
245 0300 AV 3” No 2.80 lbs
245S 0300 AV 3” Yes 2.80 lbs
245 0400 AV 4” No 3.30 lbs
245S 0400 AV 4” Yes 3.30 lbs
245 0600 AV 6” No 5.50 lbs
245S 0600 AV 6” Yes 5.50 lbs
245 0800 AV 8” No 9.20 lbs
Flanged models
245F 0400 AV 4” No 6 lbs
245FS 0400 AV 4” Yes 6 lbs
245F 0600 AV 6” No 9.10 lbs
245FS 0600 AV 6” Yes 9.10 lbs
245F 0800 AV 8” No 14.50 lbs
245F 1000 AV 10” No 20 lbs

General:

This lightweight, spring-loaded emergency vent (pressure relief only) is used on aboveground storage tanks, as a code requirement, to help prevent the tank from becoming over-pressurized and possibly rupturing if ever exposed to fire. This vent must be used in conjunction with a “normal vent.” Correct application of this vent requires proper vent size and selection for the tank system in order to meet the specific venting capacity.

WARNING: DO NOT FILL OR UNLOAD FUEL FROM A STORAGE TANK UNLESS IT IS CERTAIN THAT THE TANK VENTS WILL OPERATE PROPERLY. Morrison tank vents are designed only for use on shop fabricated atmospheric tanks which have been built and tested in accordance with UL 142, NFPA 30 & 30A, and API 650 and in accordance with all applicable local, state and federal laws. In normal operation, dust and debris can accumulate in vent openings and block air passages. Certain atmospheric conditions such as a sudden drop in temperature, below freezing temperatures, and freezing rain can cause moisture to enter the vent and freeze which can restrict internal movement of vent mechanisms and block air passages. All storage tank vent air passages must be completely free of restriction and all vent mechanisms must have free movement in order to insure proper operation. Any restriction of airflow can cause excessive pressure or vacuum to build up in the storage tank, which can result in structural damage to the tank, fuel spillage, property damage, fire, injury, and death. Monthly inspection, and immediate inspection during freezing conditions, by someone familiar with the proper operation of storage tank vents, is required to insure venting devices are functioning properly before filling or unloading a tank. Normal vents such as pressure vacuum and updraft vents for aboveground storage tanks should be sized according to NFPA 30 (2008) 21.4.3