245F Emergency Tank Vent, 8 in, Flanged, Lightweight, Morrison Bros 245F--0800 AV
245F Emergency Tank Vent, 8 in, Flanged, Lightweight, Morrison Bros 245F--0800 AV
Downloads:
Quick Specs:
- Size: 8"
- Part Number: 245F--0800 AV
- Manufacturer: Morrison Bros
- Series: Fig. 245F
- Material: Aluminum
- Type: Emergency Tank Vent
Features & Ordering:
Construction Details
- Body is aluminum
- Cover is aluminum
- Seat is FKM
Code Compliance
When properly sized for the tank, this vent will conform to the requirements of the International Fire Code; National Fire Code of Canada; National Fire Protection Agency—NFPA 20, 30, 30A, 31, 37, 110; Petroleum Equipment Institute—PEI RP200, PEI RP800; Underwriters Laboratories Inc.—UL-142, UL-2085, UL-2244; Underwriters Laboratories of Canada—CAN/ULC S601, CAN/ULC S602, CAN/ULC S652
Approvals
Underwriters Laboratories Inc. UL-2583
Product Ordering Instructions
Fig | Suffix | Size | Screen | Weight |
Male Threaded models | ||||
245M | 0200 AV | 2” | No | .50 lbs |
245MS | 0200 AV | 2” | Yes | .50 lbs |
245M | 0300 AV | 3” | No | 2.50 lbs |
245MS | 0300 AV | 3” | Yes | 2.50 lbs |
245M | 0400 AV | 4” | No | 4.50 lbs |
245MS | 0400 AV | 4” | Yes | 4.50 lbs |
245M | 0600 AV | 6” | No | 6.20 lbs |
245MS | 0600 AV | 6” | Yes | 6.20 lbs |
245M | 0800 AV | 8” | No | 10.10 lbs |
Female Threaded models | ||||
245 | 0300 AV | 3” | No | 2.80 lbs |
245S | 0300 AV | 3” | Yes | 2.80 lbs |
245 | 0400 AV | 4” | No | 3.30 lbs |
245S | 0400 AV | 4” | Yes | 3.30 lbs |
245 | 0600 AV | 6” | No | 5.50 lbs |
245S | 0600 AV | 6” | Yes | 5.50 lbs |
245 | 0800 AV | 8” | No | 9.20 lbs |
Flanged models | ||||
245F | 0400 AV | 4” | No | 6 lbs |
245FS | 0400 AV | 4” | Yes | 6 lbs |
245F | 0600 AV | 6” | No | 9.10 lbs |
245FS | 0600 AV | 6” | Yes | 9.10 lbs |
245F | 0800 AV | 8” | No | 14.50 lbs |
245F | 1000 AV | 10” | No | 20 lbs |
General:
This lightweight, spring-loaded emergency vent (pressure relief only) is used on aboveground storage tanks, as a code requirement, to help prevent the tank from becoming over-pressurized and possibly rupturing if ever exposed to fire. This vent must be used in conjunction with a “normal vent.” Correct application of this vent requires proper vent size and selection for the tank system in order to meet the specific venting capacity.
WARNING: DO NOT FILL OR UNLOAD FUEL FROM A STORAGE TANK UNLESS IT IS CERTAIN THAT THE TANK VENTS WILL OPERATE PROPERLY. Morrison tank vents are designed only for use on shop fabricated atmospheric tanks which have been built and tested in accordance with UL 142, NFPA 30 & 30A, and API 650 and in accordance with all applicable local, state and federal laws. In normal operation, dust and debris can accumulate in vent openings and block air passages. Certain atmospheric conditions such as a sudden drop in temperature, below freezing temperatures, and freezing rain can cause moisture to enter the vent and freeze which can restrict internal movement of vent mechanisms and block air passages. All storage tank vent air passages must be completely free of restriction and all vent mechanisms must have free movement in order to insure proper operation. Any restriction of airflow can cause excessive pressure or vacuum to build up in the storage tank, which can result in structural damage to the tank, fuel spillage, property damage, fire, injury, and death. Monthly inspection, and immediate inspection during freezing conditions, by someone familiar with the proper operation of storage tank vents, is required to insure venting devices are functioning properly before filling or unloading a tank. Normal vents such as pressure vacuum and updraft vents for aboveground storage tanks should be sized according to NFPA 30 (2008) 21.4.3